NEC Motor Load Calculations Example

NEC Motor Load Calculations Example

Electrical 101

2 года назад

86,564 Просмотров

Ссылки и html тэги не поддерживаются


Комментарии:

@soundman2604
@soundman2604 - 22.12.2022 04:16

Very well laid ou,t with Code articles as references. Nice job!

Ответить
@Primez8902
@Primez8902 - 21.02.2023 07:14

You dont need the FLA to do these calculations?

Ответить
@stevenwarren206
@stevenwarren206 - 21.02.2023 20:25

The overloads are calculated at nameplate FLA, right? Everything else is calculated from the FLC from from 430 tables , am I right about this?

Ответить
@JesusCruz-wt2zp
@JesusCruz-wt2zp - 23.02.2023 21:35

Your videos are great. Please do more ..

Ответить
@aaronwidder9624
@aaronwidder9624 - 28.02.2023 19:10

I thought if you rated your ocp at 250% it would be the next "lowest" size breaker or if it's sized at 125% it would be the next "highest" size breaker? Great Info sir! 👍

Ответить
@Mike-ec4zp
@Mike-ec4zp - 18.03.2023 23:23

Where does table 430.22(E) fall in these steps? If asked for any of these rating percentages? Answer be helpful

Ответить
@mcarroll598
@mcarroll598 - 03.05.2023 12:42

Wouldn’t you size your OVERLOADS to your FLA on the motor? Not your FLC from the code book?

Ответить
@mcarroll598
@mcarroll598 - 03.05.2023 12:46

When you size breakers for motors, wouldn’t you round down to the next standard circuit breaker size?

Ответить
@controlsgirl
@controlsgirl - 03.05.2023 20:48

Great example!! Way to walk through it!

Ответить
@natename797
@natename797 - 31.05.2023 02:51

Why is the first wire size not # 18?

Ответить
@oscar27ization
@oscar27ization - 05.06.2023 19:30

I think you made a small mistake by multiplying your overload protection device with your FULL LOAD CURRENT instead of your FULL LOAD AMP??

Ответить
@purpleraptor1183
@purpleraptor1183 - 14.06.2023 22:15

I am doing 50 HP [FLC= 65A, 65A*125% = 81.25A got Conductor size AWG 4] and 250 HP [FLC= 302A, 302A*125% = 377.5A got Conductor size AWG 500MCM table 310.16(75 ,Copper)]. For 50 HP - I am doing 65 A * 250% = 162.5 Amp breaker. But from ugly book, for 50 HP size breaker-150A. Same for 250 HP - 302 * 250% = 755 A. Should I not go up and standard size of breaker?

Ответить
@narendergodara1992
@narendergodara1992 - 19.06.2023 06:37

EXCELLENT VEDIO👌👌🙏🙏

Ответить
@cevtongooden1836
@cevtongooden1836 - 28.06.2023 12:10

Thanks so much send more

Ответить
@danielgriffin2674
@danielgriffin2674 - 21.07.2023 05:46

Some guys are just cut out to be teachers, nice job.

Ответить
@stuffthings9618
@stuffthings9618 - 04.08.2023 00:58

Arent you supposed to calculate the Overload from nameplate amps????

Ответить
@kythuatcongnghiep8559
@kythuatcongnghiep8559 - 06.08.2023 15:50

thank you, very helpfully for me

Ответить
@BobbaFett312
@BobbaFett312 - 04.09.2023 22:46

i have same question as others on using 75C when ampacity column. 75C can be used only when terminations are also 75C. why is 75C used here?

Ответить
@TheMadhatter0710
@TheMadhatter0710 - 08.09.2023 06:10

Information is thrown out very thoroughly. Thumbs up!

Ответить
@wadetaney8642
@wadetaney8642 - 26.09.2023 18:44

Well put!! Great teacher.

Ответить
@Sincoola27
@Sincoola27 - 08.10.2023 02:23

I took this guys full prep class a few years ago. Passed my masters exam on the first try thanks to it! great teacher

Ответить
@mr.write1433
@mr.write1433 - 15.10.2023 21:29

what nec edition is this ?

Ответить
@kentbinaoro9164
@kentbinaoro9164 - 27.10.2023 05:13

I am now very confused, but anyways I only know things for residential wiring only, I thought 14awg must use 15a breaker to protect the wire

Ответить
@Tito-nw6te
@Tito-nw6te - 12.11.2023 18:11

How can i get these work sheets ??

Ответить
@orangaharris640
@orangaharris640 - 28.11.2023 07:28

Beginer here.. dont understand most of it 😅

Ответить
@jass1989
@jass1989 - 01.01.2024 06:37

Last i checked. 1.4 was less than 1.5

Mis heard him

Ответить
@Kowloonhongkong
@Kowloonhongkong - 08.01.2024 19:33

why dont protect the wire?

Ответить
@alexramos9459
@alexramos9459 - 23.01.2024 03:57

So I just did this by calculator and field knowledge on wires and experience wiring things actual amperage it’s 7.7 not 6 learning ohms law helps a lot and makes easy to calculate by using the calculator

Ответить
@MensLifestyle1985
@MensLifestyle1985 - 29.01.2024 19:28

For Step #6, why wouldn't you add 150A to 20A for the remaining motor? Why did you only add the FLC and not the Branch Circuit protection from step #4 like you did for the larger motor?

Ответить
@kylecropanese8744
@kylecropanese8744 - 16.02.2024 03:36

Thank you so much about to go for my exam shitting bricks this helps so much

Ответить
@pingpongpaddlehead
@pingpongpaddlehead - 05.04.2024 05:26

fascinating

Ответить
@CallmeDr773
@CallmeDr773 - 07.05.2024 04:59

Super helpful! Thank you

Ответить
@thanmaysudev
@thanmaysudev - 19.05.2024 00:19

Could you please tell me why the 40hp motor doesn't have any starter

Ответить
@Luminous116
@Luminous116 - 20.06.2024 07:31

I've noticed you use 75° column for the branch ckt conductor size. However I was told to use 60°C column for circuits rated 100 amperes or less (per NEC 110.14-C) regardless of conductor insulation rating. Was there an exception that I missed?

Ответить
@juliorojas7276
@juliorojas7276 - 14.07.2024 23:08

Service factor is 1.4 and the code is 1.5 or grater to be × 125%. If is not 1.5 por greater it should be × 1.15.

Ответить
@mr.write1433
@mr.write1433 - 11.08.2024 13:33

FLA not equal to flc? Why put FLC?

Ответить
@scottdonahue6417
@scottdonahue6417 - 29.08.2024 03:51

There is a standard 70 amp breaker by the way

Ответить
@paasdfasd
@paasdfasd - 11.09.2024 23:45

what happens if the motor is 400V AC?

Ответить
@TheKaracay
@TheKaracay - 22.09.2024 17:36

he messed up on overload for big motor other than that I like the way he teaches

Ответить
@hebrewlessons2348
@hebrewlessons2348 - 08.10.2024 18:51

great great great instruction!

Ответить
@MrTomObama
@MrTomObama - 11.11.2024 21:25

On step #3 if its THWN-2 at 9.5 amps wouldn't the answer be 18 for copper? Or is it 14 because of the temp rating? Confused. I understand how you got the answer for the 65 amps just not the 9.5 amps.

Ответить
@rigobertoruiz6136
@rigobertoruiz6136 - 12.11.2024 16:37

Amazing video thanks!

Ответить
@AlfredAAwe
@AlfredAAwe - 23.01.2025 20:13

How do we factor distance when calculating wire size?

Ответить
@jaxonprice127
@jaxonprice127 - 06.03.2025 05:31

Thank You!!

Ответить
@theJaseEdwards
@theJaseEdwards - 13.04.2025 06:59

How do I get a copy of all these steps?

Ответить
@MrOsama22
@MrOsama22 - 05.05.2025 14:40

The way you calculated magnetic only CB current isn't correct , this is the Magnetic trip current not the rated current

Ответить
@DMES-wp2fj
@DMES-wp2fj - 28.05.2025 18:52

I think the wires are undersized, and the main CB is undersized. The wires should be 2 or 1 levels up the ampere rating of their circuit breaker. Load < breaker amp < wire amp. Instead, you are taking into account the overload relay.

Ответить
@JosegLicea-u9e
@JosegLicea-u9e - 14.06.2025 20:17

I think there's a mistake on step 2, you should calculate overload with FLA nameplate, not FLC and there is not fuses 0r brakes 7.6 or 65 amps on table 240.6 A nec2023 for overload

Ответить